18 AWG 2 C SOLID PLENUM – SHIELDED (SIEMENS)

18 AWG 2 conductors solid bare copper wire, plenum rated PVC insulation, shielded, and an overall plenum rated PVC jacket

APPLICATION

18 AWG 2 conductors solid bare copper wire, plenum rated PVC insulation, shielded, and an overall plenum rated PVC jacket

PART NUMBER

4360PL-SOLID

STANDARDS

• Suitable for installation under NEC (NFPA 70) articles 800, 725 and 760 guidelines S
• Suitable for installation in Canada under Section 60 of CEC, Part I
• C(UL)US listed as CMP per UL standard 444 and per CSA C22.2 No. 214-17
• UL listed as CL3P per UL standard 13 or FPLP per UL standard 1424
• Meets NFPA 262 (Steiner tunnel) flame test
• Meets RoHS 2002/95/EC Directive, RoHS 2 2011/65/EU Directive, RoHS 3 2015/863/EU Directive
• REACH compliant per Regulation (EC) No 1907/2006 (235) Updated June 14, 2023
• Operating Voltage: 300V RMS
• Made in the USA

JACKET COLORS

WHITE

JACKET

Plenum Rated Polyvinylchloride

CONDUCTORS

18 AWG SOLID; ANNEALED BARE COPPER

COLOR CODE

BLACK, RED

IMPEDANCE

35 Ω ± 10%

CAPACITANCE

54 pF/ft.

DC RESISTANCE

6.35 Ω/Mft. @ 20°C (Maximum)

INSULATION

PLENUM RATED POLYVINYLCHLORIDE

ASSEMBLY

SHIELDED; ALUMINUM MYLAR TAPE – 100% COVERAGE WITH 20 AWG 7 STRAND TINNED COPPER

RIPCORD

YES

AWG

18

CONDUCTOR

2

STRANDING

SOLID

NOMINAL LAY LENGTH (LHL - INCHES)

1,75

INSULATION THICKNESS (INCHES)

0,009

JACKET WALL THICKNESS (INCHES)

0,015

OVERAL DIAMETER (INCHES)

.149 ± .015

NET WEIGHT

22

VOLTAGE

300

Premium Wire & Cable Materials for Longevity & Durability

Premium Wire & Cable Materials for Longevity & Durability